Title 9 BUILDINGS AND CONSTRUCTION
Chapter 9.01 CALIFORNIA BUILDING STANDARDS CODE
9.01.020 Amendments to the 2007 California Building Standards Code, Part 2, known as the California Building Code.
Based upon the foregoing findings, the California Building Standards Code,
2007 Edition, is hereby amended in the following manner:
The following
provisions of the International Building Code, 2006 Edition, as published by the
International Code Council are hereby adopted: Appendices, Chapter 1
Administration with amendments; C - Group U - Agricultural Buildings; F -
Rodentproofing; G - Flood-Resistant Construction; I - Patio Covers.
A. 2007
California Building Standards Code Appendix Chapter 1-
Administration.
1. Section 105.3.2 “Time limitation of
application” is amended as follows:
Delete ...for additional periods not exceeding 90 days each. Add ... for
an additional period of 180 days.
2. Section 105.5
“Expiration” is amended as follows:
Add ...is suspended or abandoned for a period of 180 days after the time
the work is commenced, or if the owner or his/her agent fails to request an
inspection within 180 days from the previous inspection or the permit issuance
date and fails to demonstrate to the building official significant progress
toward completion of the project.
3. Section 108.3 “Building
permit valuations” is amended as follows:
Add ... The applicant for a permit shall provide an estimated permit value
at the time of application when requested by the Building
Official.
4. Section 109.3.5 “Lath and gypsum board
inspection” is amended as follows:
Delete the exception: Gypsum board that is not part of a
fire-resistance-rated assembly or a shear assembly.
5. Section 110.2
“Certificate issued” is amended as follows:
Add ...After the building official and other inspectors from other
departments or agencies inspects the building, structure or other required
features and finds no violations of the provisions of this code or other laws
that are enforced by the building department or other departments or agencies,
the building official shall issue a final for the permit that will constitute a
certificate of occupancy.
Delete items numbered 1 through 12.
6. Section 110.3
“Temporary occupancy” is amended as follows:
Delete entire section.
B. 2007 California Building Standards Code
Section 1505 Fire Classification.
1. Section 1505.1 “General” is
amended as follows:
Delete ...The minimum roof coverings installed on buildings shall comply
with Table 1505.1 based on the type of construction of the building.
Delete Table 1505.1.
2. Section 1505.1.1 “Real coverings
within very high fire hazard severity zones” is amended as
follows:
Add ... Roof coverings within very high fire hazard severity zones and/or
Wildland-Urban Interface Fire Areas.
Delete ... 50 percent add 10 percent.
3. Section 1505.1.3
“Roof coverings within all other areas” is amended as
follows:
Delete ... 50 percent add 10 percent.
Delete ... Class C add Class B.
4. Subsection B of this section is
amended as follows:
Delete section.
a. 2001 California Building Standards Code Section
2329.11.3, items 5 and 7 are amended as follows:
i. Item 5 which allows
the use of gypsum board for bracing is deleted.
ii. Item 7 is amended to
read as follows:
Portland cement plaster on studs spaced 16 inches on center installed in
accordance with Table No. 25-1. Limited to one story R-3 and U-1 occupancy
structures.
C. 2007 California Building Standards Code Section 1614A
Modifications to ASCE 7.
1. Section 1614A.1.7 ASCE 2007 California Building
Code Section 1614A is amended to read as follows:
Modification to ASCE 7, Section 12.8.1.1. Modify ASCE 7 Section 12.8.1.1
by amending Equation 12.8-5 as follows:

2. Section
1614A.1.32 Minimum Building Separation. Modification to ASCE 7, Section 12.12.3.
Replace ASCE 7 Section 12.12.3 as follows:
12.12.3 Minimum Building Separation. All structures shall be separated
from adjoining structures. Separations shall allow for the maximum inelastic
response displacement (ΔM). ΔM shall be
determined at critical locations with consideration for both translational and
torsional displacements of the structure as follows:

where δ
max is the calculated
maximum displacement at Level x as define in ASCE 7 Section 12.8.4.3.
Adjacent buildings on the same property shall be separated by at least a
distance ΔMT, where

and Δ
M1 and Δ
M2 are
the maximum inelastic response displacements of the adjacent
buildings.
Where a structure adjoins a property line not common to a public way, the
structure shall also be set back from the property line by at least the
displacement, ΔM, of that structure.
Exception: Smaller separations or property line setbacks shall be permitted
when justified by rational analysis.
D. 2007 California Building
Standards Code Section 1704.4 Concrete Construction.
1. Section 1704.4
Concrete Construction. The special inspections and verifications for concrete
construction shall be as required by this section and Table 1704.4.
EXCEPTIONS: Special inspection shall not be required for:
Isolated spread concrete footings of buildings three stories or less in
height that are fully supported on earth or rock, where the structural design of
the footing is based on a specified MPa strength, f’c, no greater than
2,500 pounds per square inch (psi) (17.2 MPa).
E. 2007 California
Building Standards Code Chapter 23 Wood.
1. Table 2305.3.4 “MAXIMUM
SHEAR WALL DIMENSION RATIOS” is amended as follows:
Delete ... Gypsum Board, gypsum lath, cement plaster from the
table.
2. Section 2305.3.9 “Summing shear capacities” is
amended as follows:
Delete ... the Exception.
3. Section 2306.4.5 “Shear walls
sheathed with other materials” is amended as follows:
Delete Section 2306.4.5
4. Table 2306.4.5 “ALLOWABLE SHEAR
FOR WIND OR SEISMIC FORCES FOR SHEAR WALLS OF LATH AND PLASTER OR GYPSUM BOARD
WOOD FRAMED WALL ASSEMBLIES” is amended as follows:
Delete Table 2306.4.5.
5. Section 2308.9.3 “Bracing”
is amended as follows:
Delete method 5 Gypsum board... and any references to method 5.
Delete method 7 Portland cement plaster...and any references to method
7.
6. Table 2308.12.4 “WALL BRACING IN SEISMIC DESIGN CATEGORIES D
AND E” is amended as follows:
Delete all references to gypsum board, fiberboard, particalboard, lath and
plaster or gypsum sheathing boards; at footnote b.
Delete all references to gypsum board, gypsum sheathing board, gypsum lath
and Portland cement plaster at footnote c.
F. 2007 California Building
Standards Code Section 2505 Shear Wall Construction.
1. Section 2505.1
“Resistance to shear (wood framing)” is amended as
follows:
Delete section 2505.1.
2. This Section Part 1: Seismic Zone 4
Near-Source Factor, Part 2: Structural Systems, Part 3: Load and Resistance
Factor Design, Part 4: Seismic Design Provisions for Structural Steel, Part 8:
Basic Load Combinations, Part 9: Detailing Requirements in Seismic Zones 3 and
4, Part 10 Calculated Story Drift and Part 11: Design Specifications is amended
as follows:
Delete Parts 1, 2, 3, 4, 8, 9, 10 and 11.
D. Findings And Modifications For Special Structural
Considerations
PART 1: SEISMIC ZONE 4 NEAR-SOURCE FACTOR (UBC
1629.4.2)
The amendment set forth in this Part 1 reasonably necessary because of the
following local geological conditions.
FINDINGS:
1. The San Francisco- San Jose Bay area region is densely populated and
located in an area of high seismic activities as indicated by United States
Geological Survey and California Division of Mines and Geology.
2. Recent earthquake activities, including the 1989 Loma Prieta and the
1994 Northridge earthquakes, have indicated the lack of adequate design and
detailing as a contributing factor to damages that reduced the protection of the
life-safety of building occupants.
3. Sections 9.6a and 9.6b of AISC - Seismic Part 1 exempts
strong-column/weak-beam requirements under certain load conditions and
configurations for steel Special and Intermediate moment frames. 97 UBC Section
1629.4.2 item 4 require that structures located near fault shall comply with
Strong Column/Week beam requirements. The revision reflects the same
requirements as in 1997 AISC-Seismic. This is consistent with SEAOC Seismology
position.
FINDINGS:
The text of UBC section 1629.4.2 is deleted and replaced with the
following:
In Seismic Zone 4, each site shall be assigned a near-source factor in
accordance with Table 16-S and the Seismic Source Type set forth in Table 16-U.
The value of Na used in determining Ca need not exceed 1.1
for structures complying with all the following conditions:
1. The soil profile type is SA, SB, SC or
SD.
2. p= 1.0.
3. Except in single-story structures, Group R, Division 3 and Group U,
Division 1 Occupancies, moment frame systems designated as part of the
lateral-force-resisting system shall be special moment-resisting
frames.
4. The provisions in Sections 9.6a and 9.6b of AISC - Seismic Part 1 shall
not apply, except for columns in one-story buildings or columns at the top story
of multistory buildings.
5. None of the following structural irregularities is present: Type 1, 4
or 5 of Table 16-L, and Type 1 or 4 of Table 16-M.
PART 2:
STRUCTURAL SYSTEMS
(UBC TABLE 16-N)
The amendment set forth in this Part 2 is reasonably necessary because of
the following local geological conditions.
FINDINGS:
1. The San Francisco — San Jose Bay area region is densely populated
and located in an area of high seismic activities as indicated by United States
Geological Survey and California Division of Mines and Geology.
2. Recent earthquake activities, including the 1989 Loma Prieta and the
1994 Northridge earthquakes have indicated the lack of adequate design and
detailing as a contributing factor to damages that reduced the protection of the
life-safety of building occupants.
3. The amendment allows the use of steel Ordinary Moment Frames and
Intermediate Moment frames with certain limitations on height and dead
load.
4. Table 16-N is revised to make it consistent with the adoption of 1997
AISC-Seismic Provisions and the latest Supplements. These provisions are
fundamentally updated from previous editions. It has incorporated to the extent
possible, most recent findings from the FEMA funded SAC Reports on steel moment
frames that.
AMENDMENT:
Table 16-N of the California Building Code is deleted and replaced with
the following:
TABLE 16-N — STRUCTURAL SYSTEMS
1
|
BASIC STRUCTURAL SYSTEM2
|
LATERAL-FORCE-RESISTING SYSTEM DESCRIPTION
|
R
|
Ω
|
HEIGHT LIMIT FOR SEISMIC ZONES 3 AND 4 (feet)
|
|
|
|
|
x 304.8 for mm
|
|
1. Bearing wall system
|
1. Light-framed walls with shear panels
|
|
|
|
|
a. Wood structural panel walls for structures three stories or less
|
5.5
|
2.8
|
65
|
|
b. All other light-framed walls
|
4.5
|
2.8
|
65
|
|
2. Shear walls
|
|
|
|
|
a. Concrete
|
4.5
|
2.8
|
160
|
|
b. Masonry
|
4.5
|
2.8
|
160
|
|
3. Light steel-framed bearing walls with tension-only bracing
|
2.8
|
2.2
|
65
|
|
4. Braced frames where bracing carries gravity load
|
|
|
|
|
a. Steel
|
4.4
|
2.2
|
160
|
|
b. Concrete3
|
2.8
|
2.2
|
- 3
|
|
c. Heavy timber
|
2.8
|
2.2
|
65
|
|
2. Building frame system
|
1. Steel eccentrically braced frame (EBF)
|
7.0
|
2.8
|
240
|
|
2. Light-framed walls with shear panels.
|
|
|
|
|
a. Wood structural panel walls for structures three stories or less
|
6.5
|
2.8
|
65
|
|
b. All other light-framed walls
|
5.0
|
2.8
|
65
|
|
3. Shear walls
|
|
|
|
|
a. Concrete
|
5.5
|
2.8
|
240
|
|
b. Masonry
|
5.5
|
2.8
|
160
|
|
4. Ordinary braced frames
|
|
|
|
|
a. Steel6
|
5.6
|
2.2
|
356
|
|
b. Concrete3
|
5.6
|
2.2
|
-
|
|
c. Heavy timber
|
5.6
|
2.2
|
65
|
|
5. Special concentrically braced frames
|
|
|
|
|
a. Steel
|
6.4
|
2.2
|
240
|
|
3. Moment-resisting frame system
|
1. Special moment-resisting frame (SMRF)
|
|
|
|
|
a. Steel
|
8.5
|
2.8
|
N.L.
|
|
b. Concrete4
|
8.5
|
2.8
|
N.L.
|
|
2. Masonry moment-resisting wall frame (MMRWF)
|
6.5
|
2.8
|
160
|
|
3. Intermediate moment-resisting frame (IMRF)
|
|
|
|
|
a. Steel6
|
4.5
|
2.8
|
356
|
|
b.Concrete5
|
5.5
|
2.8
|
-3
|
|
4. Ordinary moment-resisting frame (OMRF)
|
|
|
|
|
a. Steel6
|
3.5
|
2.8
|
-6
|
|
b. Concrete8
|
3.5
|
2.8
|
-3
|
|
5. Special truss moment frames of steel (STMF)
|
6.5
|
2.8
|
240
|
|
4. Dual systems
|
1. Shear walls
|
|
|
|
|
a. Concrete with SMRF
|
8.5
|
2.8
|
N.L.
|
|
b. Concrete with steel OMRF (Not Permitted)
|
-
|
-
|
-
|
|
c. Concrete with concrete IMRF5
|
6.5
|
2.8
|
-5
|
|
d. Masonry with SMRF
|
5.5
|
2.8
|
160
|
|
e. Masonry with steel OMRF (Not Permitted)
|
-
|
-
|
-
|
|
f. Masonry with concrete IMRF3
|
4.2
|
2.8
|
-3
|
|
g. Masonry with masonry MMRWF
|
6.0
|
2.8
|
160
|
|
2. Steel EBF
|
|
|
|
|
a. With steel SMRF
|
8.5
|
2.8
|
N.L.
|
|
b. With steel OMRF (Not Permitted)
|
-
|
-
|
-
|
|
3. Ordinary braced frames (Not Permitted)
|
|
|
|
|
4. Special concentrically braced frames
|
|
|
|
|
a. Steel with steel SMRF
|
7.5
|
2.8
|
N.L.
|
|
b. Steel with steel OMRF (Not Permitted)
|
-
|
-
|
-
|
|
5. Steel IMRF (Not permitted)
|
|
|
|
|
5. Cantilevered column building systems
|
1. Cantilevered column elements
|
2.2
|
2.0
|
357
|
|
6. Shear wall-frame interaction systems
|
1. Concrete8
|
5.5
|
2.8
|
160
|
|
7. Undefined systems
|
See Section 1629.6.7 and 1629.9.2
|
-
|
-
|
-
|
N.L.— no limit
1 See Section 1630.4 for combination of structural
systems.
2 Basic structural systems are defined in Section 1629.6.
3 Prohibited in Seismic Zones 3 and 4.
4 Includes precast concrete conforming to Section
1921.2.7.
5 Prohibited in Seismic Zones 3 and 4, except as permitted in
Section 1634.2.
6 In Seismic Zone 4 Steel IMRF, OMRF and Ordinary Braced Frames
are permitted as follows:
a) Steel IMRF are permitted for structural systems 35 feet or less in
height and the dead load of the roof, walls or floors not exceeding 35 psf each;
or for single-story buildings 60 feet or less in height with the dead load of
the roof or walls not exceeding 15 psf each where the moment joints of field
connections are constructed of bolted end plates; or single-family dwellings
using light frame construction with R = 3.0 and Ωo = 2.2.
b) Steel OMRF are permitted for buildings 35 ft or less in height with the
dead load of the roof, walls or floors not exceeding 15 psf each; or
single-story buildings 60 ft or less in height with the dead load of the roof or
walls not exceeding 15 psf each and where the moment joints of field connections
are constructed of bolted end plates.
c) Steel Ordinary Braced Frames are permitted for structural systems 35 ft
or less in height; or penthouse structures; or single-story buildings 60 ft or
less in height with the dead load of the roof or walls not exceeding 15 psf
each.
7 Total height of the building including cantilevered
columns.
8 Prohibited in Seismic Zones 2A, 2B, 3 and 4. See Section
1633.2.7.
PART 3:
LOAD AND RESISTANCE FACTOR DESIGN
UBC
2204.1
The amendment set forth in this Part 3 reasonably necessary because of the
following local geological conditions.
FINDINGS:
1. The San Francisco — San Jose Bay area region is densely populated
and located in an area of high seismic activities as indicated by United States
Geological Survey and California Division of Mines and Geology.
2. Recent earthquake activities, including the 1989 Loma Prieta and the
1994 Northridge earthquakes, have indicated the lack of adequate design and
detailing as a contributing factor to damages that reduced the protection of the
life-safety of building occupants.
3. The amendment eliminates references to Divisions II and III of Chapter
22 for seismic design of steel structures. This is necessary since the 1997 AISC
Seismic Provisions with Supplement 1 and 2 are adopted in another part of this
ordinance as the code for seismic design of such structures.
AMENDMENT:
The text of UBC section 2204 is deleted and replaced with the
following:
Design shall be by one of the following methods.
2204.1 Load and Resistance Factor Design. Steel design based on load and
resistance factor design method shall resist the factored load combinations of
section 1612.2 in accordance with the applicable requirements of section
2205.
2204.2 Allowable Stress Design. Steel design based on allowable stress
design methods shall resist the factored load combinations of section 1612.3 in
accordance with the applicable requirements of section 2205.
PART 4:
SEISMIC DESIGN PROVISIONS FOR STRUCTURAL
STEEL
(UBC 2205.3)
The amendment set forth in this Part 4 reasonably necessary because of the
following local geological conditions.
FINDINGS:
1. The San Francisco — San Jose Bay area region is densely populated
and located in an area of high seismic activities as indicated by United States
Geological Survey and California Division of Mines and Geology.
2. Recent earthquake activities, including the 1989 Loma Prieta and the
1994 Northridge earthquakes, have indicated the lack of adequate design and
detailing as a contributing factor to damages that reduced the protection of the
life-safety of building occupants.
3. The current 97 UBC edition is based on the outdated 1992 AISC Seismic
provisions. The proposal makes the CBC provisions consistent with the current
practice, which is based on the 1997 AISC Seismic with the 2 subsequent
Supplements printed afterward.
AMENDMENT:
The text of UBC section 2205.3 is deleted and replaced with the
following:
2205.3 Seismic Design Provisions for Structural Steel. Steel structural
elements that resist seismic forces shall, in addition to the requirements of
Section 2205.2 be designed in accordance with Division IV.
a. Monte
Sereno Municipal Code Section 9.01.020.1 is amended as follows:
Delete entire Section 9.01.020.1.
G. Modification of Division IV
and V of Chapter 22 of the California Building Code. Division IV of Chapter 22
of the California Building Code is deleted and replaced with the
following:
Division IV — SEISMIC PROVISIONS FOR STRUCTURAL STEEL
BUILDINGS
Based on Seismic Provisions for Structural
Steel
Buildings, of the American Institute of Steel Construction. Parts I and III,
dated April 15, 1997, and Supplement No. 2, dated November 10, 2000.
2210 — Adoption
Except for the modifications as set forth in Sections 2211 and 2212 of
this division and the requirements of the Building Code, the seismic design,
fabrication, and erection of structural steel shall be in accordance with the
Seismic Provisions for Structural Steel Buildings, April 15, 1997 published by
the American Institute of Steel Construction, 1 East Wacker Drive, Suite 3100,
Chicago, IL 60601, as if set out at length herein. The adoption of Seismic
Provisions for Structural Steel Buildings in this Division, hereinafter referred
to as AISC-Seismic, shall include Parts I (LRFD), and III (ASD) and Supplement
No. 2, dated November 10, 2000.
Where other codes, standards, or specifications are referred to in this
specification, they are to be considered as only an indication of an acceptable
method or material that can be used with the approval of the Building
Official.
2211 — Design Methods
When the load combinations from Section 1612.2 for LRFD are used,
structural steel buildings shall be designed in accordance with Chapter 22
Division II (AISC-LRFD) and Part I of AISC-Seismic as modified by this
Division.
When the load combinations from Section 1612.3 for ASD are used,
structural steel buildings shall be designed in accordance with Chapter 22
Division III (AISC-ASD) and Part III of AISC-Seismic as modified by this
Division.
2212 — Amendments
The AISC-Seismic adopted by this Division apply to the seismic design of
structural steel members except as modified by this Section.
a) The following terms that appear in AISC-Seismic shall be taken as
indicated in the 1997 Uniform Building Code.
|
AISC-Seismic
|
1997 Uniform Building Code
|
|
Seismic Force Resisting System
|
Lateral Force Resisting System
|
|
Design Earthquake
|
Design Basis Ground Motion
|
|
Load Combinations Eqs. (4-1) and (4-2)
|
Chapter 16 Eqs. (12-17) and (12-18) respectively
|
|
LRFD Specification Section Eqs. (A4-1) through (A4-6)
|
Chapter 16 Eqs. (12-1) through (12-6) respectively
|
|
ςoQE
|
Em
|
b) The text of section 1 of Part 1 of the AISC Seismic Provisions is
deleted and replaced with the following:
1. Scope
These provisions are intended for the design and construction of
structural steel members and connections in the Seismic Force Resisting Systems
in buildings for which the design forces resulting from earthquake motions have
been determined on the basis of various levels of energy dissipation in the
inelastic range of response. These provisions shall apply to buildings in
Seismic Zone 2 with an importance factor I greater than one, in Seismic Zone 3
and 4 or when required by the Engineer of Record.
These provisions shall be applied in conjunction with, Chapter 22,
Division II, hereinafter referred to as the LRFD Specification. All members and
connections in the Lateral Force Resisting System shall have a design strength
as provided in the LRFD Specification to resist load combinations 12-1 through
12-6 (in Chapter 16) and shall meet the requirements in these
provisions.
Part I includes a Glossary, which is specifically applicable to this Part,
and Appendix S.
c) Section 4.1. of Part 1, first paragraph of the AISC Seismic Provisions
is deleted and replaced as follows:
4.1 Loads and Load Combinations
The loads and load combinations shall be those in Section 1612.2 except as
modified throughout these provisions.
Eh is the horizontal component of earthquake load E required in
Chapter 16. Where required in these provisions, an amplified horizontal
earthquake load ΩoEh shall be used in lieu of
Eh as given in the load combinations below. The term
Ωo is the system overstrength factor as defined in chapter 16.
The additional load combinations using amplified horizontal earthquake load
are:
|
1.2 D + 0.5 L + 0.2S + ΩoEh
|
(4-1)
|
|
0.9 D + ΩoEh
|
(4-2)
|
Exception: the load factor on L in load combination 4-1 shall be equal to
1.0 for garages, areas occupied as places of public assembly and all areas where
the live load is greater than 100 psf.
Orthogonal earthquake effects shall be included in the analysis as
required in section 1633.1, except that, when consideration of the load
ΩoEh is required, orthogonal earthquake effects need
not be considered.
1. Monte Sereno Municipal Code Section 9.01.020.3 is
amended as follows:
Delete entire Section 9.01.020.3.
H. Deletion of Division V of Chapter
22 of the California Building Code.
Division V of Chapter 22 of the
California Building Code is hereby deleted.
9.01.020.3:
PART 8
BASIC LOAD COMBINATIONS
(UBC 1612.2.1)
FINDINGS:
The amendment set forth in this part reasonably necessary because of the
following local geological conditions.
1. The San Francisco — San Jose Bay area region is densely populated
and located in an area of high seismic activities as indicated by United States
Geological Survey and California Division of Mines and Geology.
2. Recent earthquake activities, including the 1989 Loma Prieta and the
1994 Northridge earthquakes, have indicated the lack of adequate design and
detailing as a contributing factor to damages that reduced the protection of the
life-safety of building occupants.
3. To avoid reduction of the vertical seismic component (Ev) by
the dead load (0.9D) which was not the intent of considering the vertical
component in seismic calculations.
4. To delete exception item 2 regarding the 1.1 factor for seismic design
of concrete and masonry. The need for eliminating this factor has been well
documented in many engineering and trade journals as well as in SEAOC Blue Book
Commentary C101.7.1 (page. 85)
AMENDMENT:
The text of Section 1612.2.1 is deleted and replaced with the
following:
1612.2.1 Basic load combinations. Where Load and Resistance Factor Design
(Strength Design) is used, structures and all portions thereof shall resist the
most critical effects from the following combinations of factored
loads:
|
1.4D
|
(12-1)
|
|
1.2D + 1.6L + 0.5 (Lr or S)
|
(12-2)
|
|
1.2D + 1.6 (Lr or S) + (f1 L or 0.8 W)
|
(12-3)
|
|
1.2D + 1.3W + (f1 L + 0.5 (Lr or S)
|
(12-4)
|
|
1.2D + 1.0E + (f1 L + f2 S)
|
(12-5)
|
|
0.9D ± (1.0ρEh or 1.3 W)
|
(12-6)
|
WHERE:
f1 = 1.0 for floors in places of public assembly, for live
loads in excess of 100 psf (4.9 kN/m2), and for garage live
load.
= 0.5 for other live loads.
f2 = 0.7 for roof configurations (such as saw tooth) that do
not shed snow off the structure.
= 0.2 for other roof configurations.
EXCEPTIONS:
1. Factored load combinations for concrete per Section 1909.2 where load
combinations do not include seismic forces.
2. Where other factored load combinations are specifically required by the
provisions of this code.
1. Monte Sereno Municipal Code Section
9.01.020.4 is amended as follows:
Delete entire section.
9.01.020.4
PART 9
DETAILING REQUIREMENTS IN SEISMIC ZONES 3 AND
4
(UBC 1630.8.2.2)
FINDINGS:
The amendment set forth in this part reasonably necessary because of the
following local geological conditions.
1. The San Francisco — San Jose Bay area region is densely populated
and located in an area of high seismic activities as indicated by United States
Geological Survey and California Division of Mines and Geology.
2. Recent earthquake activities, including the 1989 Loma Prieta and the
1994 Northridge earthquakes, have indicated the lack of adequate design and
detailing as a contributing factor to damages that reduced the protection of the
life-safety of building occupants.
3. The provision is adopted in AISC-Seismic 97 Part I, Section 8.3 and is
applicable to all axial loaded members therefore, it is redundant.
4. Old section is no longer applicable. Replaced with provision in the
AISC-Seismic.
AMENDMENT:
The text of Section 1630.8.2.2 is deleted and replaced with the
following:
1630.8.2.2 Detailing Requirements in Seismic Zones 3 and 4. In Seismic
Zones 3 and 4, elements supporting discontinuous systems shall meet the
following detailing or member limitations:
1. Reinforced concrete or reinforced masonry elements designed primarily
as axial-load members shall comply with Section 1921.4.4.5.
2. Reinforced concrete elements designed primarily as flexural members and
supporting other than light-frame wood shear wall systems or light-frame steel
and wood structural panel shear wall systems shall comply with Sections 1921.3.2
and 1921.3.3. Strength computations for portions of slabs designed as supporting
elements shall include only those portions of the slab that comply with the
requirements of these Sections.
3. Masonry elements designed primarily as axial-load-carrying members
shall comply with Sections 2106.1.12.4, Item 1, and 2108.2.6.2.6.
4. Masonry elements designed primarily as flexural members shall comply
with Section 2108.2.6.2.5.
5. Steel elements designed primarily as flexural members or trusses shall
have bracing for both top and bottom beam flanges or chords at the location of
the support of the discontinuous system and shall comply with the requirements
of AISC-Seismic Part I, Section 9.4b.
6. Wood elements designed primarily as flexural members shall be provided
with lateral bracing or solid blocking at each end of the element and at the
connection location(s) of the discontinuous system.
2. Monte Sereno
Municipal Code Section 9.01.020.5 is amended as follows:
Delete entire section.
9.01.020.5
PART 10
CALCULATED STORY DRIFT
UBC 1630.10.2
FINDINGS:
The amendment set forth in this part reasonably necessary because of the
following local geological conditions.
1. The San Francisco — San Jose Bay area region is densely populated
and located in an area of high seismic activities as indicated by United States
Geological Survey and California Division of Mines and Geology.
2. Recent earthquake activities, including the 1989 Loma Prieta and the
1994 Northridge earthquakes, have indicated the lack of adequate design and
detailing as a contributing factor to damages that reduced the protection of the
life-safety of building occupants.
3. The amendment corrects a much significant deficiency in the 97 UBC,
which eliminated any minimum base shear from consideration when checking for
building drift.
4. After engineers began using the ‘97 UBC they found problems with
applying (30-7) for the drift calculations. (30-7) applies only to Zone 4 and
was added after the Northridge Earthquake to account for near fault pulses. An
erratum to ‘97 UBC Section 1630.10.3 was issued in March 2001, 3 years
following publication, that deleted (30-7) from being applied to drift
calculations. However, SEAOC Seismology Committee found that the erratum
actually made the drift limit to be less stringent and would allow more slender
and flexible buildings than were allowed under the ‘94 UBC.
5. The proposed modification was recommended by SEAOC Seismology
Committee. It effectively makes the descending branch vary with 1/T2/3
for drift coordination purposes and make the drift limitations very
similar to those of the ‘94 UBC.
6. The change from 0.7 seconds to 0.5 seconds in the proposal is needed to
avoid a step function in the drift limit. If 0.7 second were retained, the drift
limit at T just below 0.7 seconds would have been different from the drift limit
just above 0.7 seconds. With the switch to 0.5 seconds, the drift limit just
below T=0.5 seconds is the same as the drift limit just above T=0.5
seconds
AMENDMENT:
A. The text of section 1630.10.2 is deleted and replaced with the
following:
1630.10.2 Calculated. Calculated story drift using ΔM
shall not exceed 0.025 times the story height for structures having a
fundamental period of less than 0.5 second. For structures having a fundamental
period of 0.5 second or greater, the calculated story drift shall not exceed
0.020/T1/3 times the story height.
EXCEPTIONS:
1. These drift limits may be exceeded when it is demonstrated that greater
drift can be tolerated by both structural elements and nonstructural elements
that could affect life safety. The drift used in this assessment shall be based
upon the Maximum Inelastic Response Displacement,
ΔM.
2. There shall be no drift limit in single-story steel-framed structures
classified as Groups B, F and S Occupancies or Group H, Division 4 or 5
Occupancies. In Groups B, F and S Occupancies, the primary use shall be limited
to storage, factories or workshops. Minor accessory uses shall be allowed in
accordance with the provisions of Section 302. Structures on which this
exception is used shall not have equipment attached to the structural frame or
shall have such equipment detailed to accommodate the additional drift. Walls
that are laterally supported by the steel frame shall be designed to accommodate
the drift in accordance with Section 1633.2.4.
B. The text of section 1630.10.3 is deleted and replaced with the
following:
1630.10.3 Limitations. The design lateral forces used to determine the
calculated drift may disregard the limitations of Formula (30-6) and (30-7) and
may be based on the period determined from Formula (30-10) neglecting the 30 or
40 percent limitations of Section 1630.2.2, Item 2
3. Monte Sereno
Municipal Code Section 9.01.020.6 is amended as follows:
Delete entire section.
9.01.020.6
PART 11
DESIGN SPECIFICATIONS
(UBC 2316)
FINDINGS:
The amendment set forth in this part reasonably necessary because of the
following local geological conditions.
1. The San Francisco — San Jose Bay area region is densely populated
and located in an area of high seismic activities as indicated by United States
Geological Survey and California Division of Mines and Geology.
2. Recent earthquake activities, including the 1989 Loma Prieta and the
1994 Northridge earthquakes, have indicated the lack of adequate design and
detailing as a contributing factor to damages that reduced the protection of the
life-safety of building occupants.
3. The 1991 NDS is an outdated specification, which is more than 10 years
old. Since the adoption of 97 UBC the NDS has published the 1997 specifications,
which incorporates many of the items that were added since publication of 1991
NDS and it is also in a more user friendly format.
AMENDMENTS:
A. Part 1 of UBC Chapter 23, Division III is deleted and replaced with the
following:
Part I-ALLOWABLE STRESS DESIGN OF WOOD
This standard, with certain exceptions, is the ANSI/NFoPA NDS-97 National
Design Specification for Wood Construction of the American Forest and Paper
Association, 1997 Edition, and the Supplement to the 1997 Edition, National
Design Specification, adopted by reference.
The National Design Specification for Wood Construction, 1997 Edition, and
supplement are available from the American Forest and Paper Association, 1111
19th Street, NW, Eighth Floor, Washington, DC, 20036.
B. The text of UBC section 2316.1 is deleted and replaced with the
following:
SECTION 2316 — DESIGN SPECIFICATIONS
2316.1 Adoption and Scope. The National Design Specification for Wood
Construction, revised 1997 Edition (NDS), which is hereby adopted as a part of
this code, shall apply to the design and construction of wood structures using
visually graded lumber, mechanically graded lumber, structural glued laminated
timber, and timber piles. National Design Specification Appendix Section F,
Design for Creep and Critical Deflection Applications, Appendix Section G,
Effective Column Length, and Appendix Section J, Solution of Hankinson Formula
are specifically adopted and made a part of this standard. The Supplement to the
1997 Edition National Design Specification, Tables 2A, 4A, 4B, 4C, 4D, 4E, 5A,
5B and 5C are specifically adopted and made a part of this standard.
Other codes, standards or specifications referred to in this standard are
to be considered as only an indication of an acceptable method or material that
can be used with the approval of the building official, except where such other
codes, standards or specifications are specifically adopted by this code as
primary standards.
C. Section 12 of Section 2316.2 is deleted and replaced with the
following:
12. Sec. 3.2.3.3. Add to end of paragraph as follows: Cantilevered
portions of beams less than 4 inches (102 mm) in nominal thickness shall not be
notched unless the reduced section properties and lumber defects are considered
in the design. For effects of notch on shear strength, see Section
3.4.4
D. Section 14 of Section 2316.2 is deleted.
E. Section 26 of Section 2316.2 is deleted.
F. Section 27 of Section 2316.2 is deleted.
(Ord. 156 § 1
(part), 2007: Ord. 136 § 1 (part), 2002; Ord. 115 § 1
(part), 1999)